Event ID: 1141 Source: UPS

Source
Level
Description
UPS battery is discharged: <value>.
Comments
 
As per technical support at APC, this event may be logged numerous times in the system log if the UPS battery is faulty or is failing. In my case, it occurred right after executing a runtime calibration and was followed by event id 1142. APC technical support recommends running runtime calibrations once or twice per year. In my case, I was running them every other week, which was far too frequent. Try replacing your UPS battery and do not run runtime calibrations more than recommended, this should prevent this event from reoccurring in the future.